Release of hydrocarbons and hydrogen in a refinery

Event

Event ID
901
Quality
Description
The accident occurred on one of the heat exchangers of the hydro-desulphurisation unit.
The role of the exchanger , located between the charge pumps and the furnace, was to heat the charge using the hot products from the reactor. Before the exchanger, pressurised hydrogen is injected into the charge. The exchanger was equipped with interchangeable bundles mounted with deflector plates.

During a shutdown, some beams were mistakenly reassembled upside down. When the installation restarted and the compressor of the hydrogen circuit arrived at 75% of its capacity, one of the deflectors was blown off and obstructed the inlet of the exchanger. Consequently, the safety device of the compressor triggered the compressor stop and the pressure release valves released part of the contents.
Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
Leak No Ignition (No additional details provided)
Macro-region
Europe
Country
France
Date
Main component involved?
Heat Exchanger (Pipe)
How was it involved?
Rupture
Initiating cause
Wrong Installation
Root causes
Root CAUSE analysis
The reason for the over-pressurisation of the compressor and the pressure relief activation was the block of part of the gas flow into the heat exchanger tubes bundle.

A ROOT CAUSE component was a human error occurred when re-installing the exchanger's components inverted. However, an additional factor was the failure of the supervision and final inspection procedure to detect the mistake.

Facility

Application
Petrochemical Industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected
heat exchanger
Location type
Open
Location description
Industrial Area
Operational condition
Pre-event occurrences
The desulphurisation unit was restarted after a shutdown during which component of the heat exchanger unit were (wrongly) reinstalled

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
Part of the hydrocarbon load, including hydrogen, was released to the environment.

Event Nature

Release type
gas mixture
Involved substances (% vol)
H2,
hydrocarbons
Presumed ignition source
No ignition

References

Reference & weblink

Original description of the event in database ARIA

JRC assessment