Event
- Event ID
- 835
- Quality
- Description
- In a petrochemical plant, visual inspection detects fumes under the heat insulation of a heat exchanger operating under hydrogen pressure.
The first intervention team was mobilized and the unit stopped for depressurization and cooling.
A risk analysis was conducted before erecting a scaffold, decalcifying the exchanger and inspecting it under safe conditions. After having defined the fire protection and fire prevention strategy, the operator decided to put the unit back under pressure.
During this rise in pressure, a resumption of fire on the flange justified the triggering of the emergency plan. The intervention team managed the fire.
No injuries or impacts outside the site are to be deplored.
At the time of the accident, the plant was shut down due to a staff strike. The unit, usually operated under a mixture of butane and hydrogen, according to the supplier's recommendations, was filled with hydrogen only. - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Fire (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Root causes
- Root CAUSE analysis
- A leaking seal on a flange is the cause of the accident.
Facility
- Application
- Petrochemical Industry
- Sub-application
- hydrogen heat exchanger
- Hydrogen supply chain stage
- All components affected
- heat exchanger operating under hydrogen pressure
- Location type
- Open
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- At the time of the accident, the plant was shut down due to a staff strike. The unit, usually operated under a mixture of butane and hydrogen, was filled with pure hydrogen according to supplier's recommendations.
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Post-event summary
- No injuries or impacts outside the site are to be deplored. At the time of the accident, the plant was shut down due to a staff strike.
Lesson Learnt
- Corrective Measures
The action plan put in place to reduce the probability of re-occurrence of the accident comprises:
1. the study of the possibility of cooling and re-pressurizing the heat exchanger under helium or nitrogen,
2. preventive replacement of all connections under hydrogen
3. regular technical inspection.
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Presumed ignition source
- Not reported
References
- Reference & weblink
ARIA data base <br />
event no. 26429
JRC assessment
- Sources categories
- ARIA