Event
- Event ID
- 826
- Quality
- Description
- In a laboratory, tests with hydrogen as aerospace rocket propellants were carried out.
One of the experiments consisted in the generation of a vertical jet (turbulent regime) to determine the sound levels emitted by jets of H2 gas. It consisted in the intentional venting of 1000 kg of hydrogen at 23 MPa within 30 s.
The discharge flow was uniformely increased upt to 55 kg/s, maintained for 10 seconds and then reduced to zero, After 26 s, while decreasing the flow, the hydrogen unintentionally ignited. A fireball was formed followed immediately by an explosion.
The Vapour Cloud explosion VCE caused damage to structures of the surrounding buildings (walls, doors, roofs).
The over-pressure was estimated at 0.035 bar to 45 m. The burning gas cloud of approx. 9 m diameter and 45 m height containing 9 to 10 kg of hydrogen.
According to the some sources, the cause of the ignition could have been static electricity or a spark of mechanical origin. Other sources concluded that at the release conditions of the experiment, auto-ignition can occur.
[Note of HIAD Validator: on the quantity of hydrogen involved in the explosion, the sources diverge (see reference): for ARIA it was 90 kg, for PRESLHY it was 9 kg, for Lee it was 10 kg, for ICHEME was 71 kg. ] - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- Main component involved?
- Venting System
- How was it involved?
- Ignition Of Vented H2
- Initiating cause
- Wrong Operation
- Root causes
- Root CAUSE analysis
- The INITIATING CAUSE was the unplanned ignition of a hydrogen flow during an experiment.
IGNITION was probably due to static electricity and / or a spark of mechanical origin.
The ROOT CAUSE was probably a shortcoming in the design and execution of the experiment, which did not consider the possibility of ignition and detonation.
Facility
- Application
- Laboratory / R&d
- Sub-application
- Laboratory / R&D
- Hydrogen supply chain stage
- All components affected
- laboratory, vertical jet experiment
- Location type
- Open
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- According to the Wikipedia page dedicated to the testing facility, previous accidents with hydrogen had already taken place in the year 1960-64.
This is not surprising, because the laboratory was one of the first in the world studying hydrogen properties. - Description of the facility/unit/process/substances
- For abackground information regarding this NASA project, see Wikipedia page https://en.wikipedia.org/wiki/Project_Rover#CITEREFFinseth1991 (accessed November 2025)
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Post-event summary
- VCE (mainly negative overpressure) causes damage to structures (walls, doors, roofs) of buildings. The overpressure is estimated to be 0.035bar to 45 m and the amount of H2 involved in the explosion is 90 kg (othe source says 10 kg).
Explosion was heard 3.2 km away. TNT equivalent of 8%.
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release duration
- 23 sec
- Release rate
- 55 kg/s
- Released amount
- 10 kg
- Presumed ignition source
- Static electricity
- Ignition delay
- 23
- Flame type
- Fireball
References
- Reference & weblink
Prof. J. Lee presentation at 1st European Summer School on Hydrogen Safety (ESSH)<br />
available at the HySafe project site<br />
http://www.hysafe.org/science/eAcademy/php/1stesshsprogramme.php<br />
(see slides from 13 to 15, accessed October 2020)Gummer & Hawksworth, literature review on Spontaneous ignition of hydrogen , HSE (2008) https://webarchive.nationalarchives.gov.uk/ukgwa/20241207091242/https:/… />
(accessed November 2025)Event description in the French database ARIA<br />
https://www.aria.developpement-durable.gouv.fr/accident/10095_en/?lang=… <br />
(accessed October 2020)Gugan K., Unconfined vapour cloud explosions, Institution of Chemical Engineers, 1979, ISBN 9780852951149, 0852951140
JRC assessment
- Sources categories
- Scientific article