- Description
- A leak occurred on a line connecting the hot separator to the cold separator of a refinery diesel desulphurization.
The alert was given by the activation of the fixed H2S detector.
The 30 bar pressure line contained essentially hydrogen with a high concentration of H2S. The operators stopped the unit and isolated the leak in about ten minutes. The line was pierced at a bend at 135 ° C following a bend at 90 ° C. The accident investigation showed that the presence of the elbows resulted in turbulence which created a localized depression: this configuration favoured the formation of deposits (in particular during the stops of the water wash pump). Deposition corrosion developed until the line was punctured. A 90 ° elbow inspection was performed by the site inspection department but not at 135 ° C. - Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- Leak No Ignition (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Root causes
- Root CAUSE analysis
- Localised corrosion in pipe elbows, until the line was punctured.
Facility
- Application
- Petrochemical Industry
- Sub-application
- Hydrodesulphurisation process
- Hydrogen supply chain stage
- All components affected
- process gas pipe
- Location type
- Unknown
- Location description
- Industrial Area
- Operational condition
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Post-event summary
- The operators stopped the unit and isolated the leak in about ten minutes.
Event Nature
- Release type
- gas mixture
- Involved substances (% vol)
- H2,
H2S - Design pressure (MPa)
- 3
- Presumed ignition source
- No ignition
References
- Reference & weblink
ARIA data base <br />
event no. 23175:<br />
https://www.aria.developpement-durable.gouv.fr/accident/23175/<br />
(accessed July 2024)
JRC assessment
- Sources categories
- ARIA