Fire at the desulphurisation unit of a refinery

Event

Event ID
613
Quality
Description
The explosion occurred during preparatory work to start a compressor that supplies hydrogen gas to a heavy oil direct desulfurization unit. The inspection cover of the crank case came off, injuring an operator.
Normally, nitrogen was supplied to purge the case , displacing the hydrogen leaking from the shaft seal of the compressor cylinder. The accident investigation revealed that the nitrogen flow meter was broken, causing almost no gas to flow.
It is assumed that the hydrogen leaking from the shaft seal of the cylinder entered the crankcase, ignited and burned due to static electricity. The expansion force of the explosion caused the inspection cover of the crankcase to fly off.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Asia
Country
Japan
Date
Main component involved?
Compressor / Booster / Pump (Piston)
How was it involved?
Internal Explosion (H2-Air Mixture)
Initiating cause
Inadequate Or No Purge
Root causes
Root CAUSE analysis
The INITIATING CAUSE was the failing of the nitrogen system supposed to purge the compressor crankcase free of hydrogen.
The failure to purge was due to a broken flow metre which was indicating nitrogen flow while almost no nitrogen was flowing
The ROOT CAUSE was a lack of proper inspection and maintenance.

Facility

Application
Petrochemical Industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
Hydrogen Compression (No additional details provided)
All components affected
flow meter, shaft seal,
compressor cylinder,
crankcase,
H2 compressor
Location type
Unknown
Location description
Industrial Area
Operational condition
Pre-event occurrences
Preparatory operation was ongoing for the start of a hydrogen compressor

Emergency & Consequences

Number of injured persons
1
Number of fatalities
0
Post-event summary
minor injury

Lesson Learnt

Lesson Learnt

This is an incident cause by the wrong indication of an instrument, which was a critical component of preventing measures of the system. Special attention should be given to the proper functioning of components critical to safety. Effective check/inspection shall be in place to detect early enough malfunctioning. Moreover, redundancy could be provided, for example by installing two components with the same function.

Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Presumed ignition source
Static electricity

References

Reference & weblink

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): <br />
https://www.khk.or.jp/public_information/incident_investigation/hpg_inc… />
(accessed May 2025)

The first entry in HIAD was coming from RISCAD, which is now closed.<br />

JRC assessment