- The charge pump on a hydro-desulphurissation unit tripped. The charge flow control valve then opened wide on low flow. The high pressure hydrogen supplied to the hydro-desulphurisation unit flowed backwards through a faulty non-return valve to the charge tank.
The tank vents were not designed for this high flow of gas and so the weak roof to the wall seam failed. Fortunately, the gas did not find a source of ignition and so there was no fire. The pump could have failed due to reverse rotation, but did not. - Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- Leak No Ignition (No additional details provided)
- Macro-region
- Europe
- Country
- United Kingdom
- Date
- Main component involved?
- Valve (Non-Return)
- How was it involved?
- Internal Leak
- Initiating cause
- Unknown
- Root causes
- Root CAUSE analysis
- The INITIATING cause was a mechanical equipment failure
The root cause could be perhaps found in a design or operation cause (failure of proper maintenance or inspection). The safety design did not take into account this type of event sequence. Backflow due to pump or compressor tripping is a well-known mishaps.
Facility
- Application
- Petrochemical Industry
- Sub-application
- Hydrodesulphurisation process
- Hydrogen supply chain stage
- All components affected
- desulphurisation unit, control valve, pump tank
- Location type
- Open
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- Tripping of the rector unit
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
Lesson Learnt
- Corrective Measures
According to the ICHEME database, the following measures were requested:
1. To identify all critical non-return valves which could cause a serious incident when failing. These valve have to be repaired to “as new condition” at scheduled shutdowns.
2. To identify the case where reverse flow should not be relied on as the sole means of preventing a serious incident. In those cases, to modify operations in such a way that the flow control valve close any time that the pump tripped.
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Presumed ignition source
- No ignition
References
- Reference & weblink
Event 11049 of the UK database ICHEME<br />
https://www.icheme.org/knowledge/safety-centre/resources/accident-data/… />
(accessed September 2020)
JRC assessment
- Sources categories
- ICHEME