Explosion from the hydrogen recycle line at a refinery

Event

Event ID
568
Quality
Description
Localized corrosion of a FCCU (Fluid Catalytic Cracking Unit) feed hydrotreater recycle hydrogen line by-pass around a hydrogen pre-heat exchanger led to an explosion and fire.

The failed part of the line had been identified by inspection as a dead leg. After investigation it was found that the mechanism of corrosion was ammonium chloride under deposit corrosion. The source of chloride has not been traced, but hydrogen from the catalytic reformer was strongly suspected.
There was damage to equipment, material loss and product loss.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Root causes
Root CAUSE analysis
The INITIATING CAUSE was the loss of confinement of a pipe carrying recycled hydrogen, due to internal corrosion. The report of this event is not clear on the possible causes of corrosion. Corrosion by ammonium chloride is suspected, although the source of this substance remains unknown. Moreover, the role of hydrogen is unclear.
The ROOT CAUSE was identified in an inadequate inspection of the dead leg.

Facility

Application
Petrochemical Industry
Sub-application
hydrotreatment
Hydrogen supply chain stage
All components affected
recycle hydrogen line, pre-heat exchanger
Location type
Unknown
Location description
Industrial Area
Operational condition

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
There was damage to equipment, material loss and product loss.

Lesson Learnt

Lesson Learnt

The root cause of this hydrogen release was identified in an inadequate inspection, which was unable to identify internal of the pipe carrying hydrogen.
However, localised corrosion mechanisms are difficult to detect by means of the usual detection technique based on fixed point ultra-sound testing (UT). Moreover, the prevention of internal corrosion of dead leg corrosion is difficult, because there are several different corrosion mechanisms to consider.

Event Nature

Release type
gas mixture (syngas)
Involved substances (% vol)
H2,
possbily syngas
Presumed ignition source
Not reported

References

Reference & weblink

Extract from the ICHEME database "ICHEME consequences-explosion-details", available at (accessed May 2020):<br />