Event
- Event ID
- 546
- Quality
- Description
- A leak occurred on a 4 inch hydrogen main gas line which ran along a pipe bridge at the east end of a first stage compression plant building. The relased hydrogen ignited.
The source of ignition was hot welding sparks arising from work being carried out by contract personnel whilst installing a new chlorine line above the hydrogen lineon the pipe-bridge.
Before the welding work was carried out, an explosivity test had been carried out in the area and a 0 explosive gas result had been reproted in the work permit.
An investigation into the incident found that the removed section of the hydrogen main revealed an elliptical hole 2 centimetres x 1 and a half centimetres. It was only when the lagging was disturbed that the hydrogen leak became obvious.The area around the hole in hydrogen main was very pitted suggesting that the failure was due to localised corrosion. - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Fire (No additional details provided)
- Macro-region
- Europe
- Country
- United Kingdom
- Date
- Main component involved?
- Pipe
- How was it involved?
- Leak & Formation Of A Flammable H2-Air Mixture
- Initiating cause
- Wrong Operation
- Root causes
- Root CAUSE analysis
- The INITIATING CAUSE was an elliptical hole of 2 centimetres x 1.5 centimetres.
It was very probably due to localised corrosion.
The leak was not detected during the explosivity test because of a build up of scale sealing the hole, possibly dislodged later by the activities of the contractors in the area. The technical reason for the corrosion is not povided or known.
Neverhtless, ROOT CAUSE could be possibly attributed to a lack of effective inspection, not able to detect the progress of the corrosion.
Facility
- Application
- Chemical Industry
- Sub-application
- Hydrodesulphurisation process
- Hydrogen supply chain stage
- All components affected
- Separation equipment
- Location type
- Unknown
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- Welding works were ongoing, but the plant had not been shutdown (pesene of flammabe gases had been excluded by measures).
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Hole shape
- Near Circular
- Hole length (mm)
- 2
- Hole width (mm)
- 1.5
- Presumed ignition source
- Welding
- Deflagration
- N
- High pressure explosion
- N
- High voltage explosion
- N
- Flame type
- Jet flame
References
- Reference & weblink
Event of the UK database ICHEME.<br />
https://www.icheme.org/knowledge/safety-centre/resources/accident-data/
JRC assessment
- Sources categories
- ICHEME