Explosion in an electrolyser producing chlorine

Event

Event ID
253
Quality
Description
An explosion took place in the electrolysis room of a plant producing chlorine and its derivatives. An auxiliary outgoing circuit breaker opened, due to their ageing, to the overload of the auxiliary transformer and to high temperature. In absence of power, the mercury and brine pumps and the chlorine compressors stopped.
Under normal operating conditions, the circuit breakers of the three transformers supplying the current to the auxiliary systems of three electrolysers should all open (trip) automatically when the coil power supply is interrupted.

In this case, however, one of the circuit breakers did not trip and remained closed, supplying 20 kA power to and one electrolysis room. The explosion occurred when the auxiliary transformer was finally closed after several attempts, 15 minutes later. The chlorine main collector upstream of the compressor was destroyed, 15 electrolytic cells were seriously damaged, but no casualty was reported.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Main component involved?
Electrolytic Cell
How was it involved?
Internal Explosion (H2-Cl2 Mixture)
Initiating cause
Malfunctioning (Electrical/Electronic Component)
Root causes
Root CAUSE analysis
Since the malfunctioning circuit breaker was found in good condition and had been in operation for 2 years, the most probable explanation was the presence of a strong magnetic field generated by the nearby 50 kA conductors, which could have either excited the coil or induced a residual magnetisation of the breaker core.

A plausible cause for explosion was the formation hydrogen by the acidic attackat the bottom of the cells and production of sodium and potassium hypochlorite. The still running chlorine compressor extracted the hydrogen and reacted with the chlorine remaining in the pipe.

As the operator did not realise that the circuit breaker was not closed, he did not prohibit the reactivation of all auxiliary circuit breakers, as he should have done.

Facility

Application
Chemical Industry
Sub-application
Chlorine production
Hydrogen supply chain stage
All components affected
electrolyser, circuit breaker
Location type
Unknown
Location description
Industrial Area
Operational condition
Pre-event occurrences
The circuit breaker which did not operate was in good state and only two years old.

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
The common chlorine collector and various compressors were destroyed. The electrolyser unit where the explosion took place was heavily damaged. No injuries among the personnel.
Emergency action
The mitigating strategy worked as planned. The flammable gas detectors alarmed the operative room and the plant was shut down, the reactor purged with nitrogen, and the affected reactor components were cooled by the fire brigade. The fire was extinguished by 5 minutes.

Lesson Learnt

Corrective Measures
(1) Instructions were amended,
(2) Safety devices were installed to prevent magnetisation of the components of the circuit breakers,
(3) Provisions were made to reduce the power load of the circuit breaker of the auxiliary components.

Event Nature

Release type
Gas mixture
Involved substances (% vol)
H2,
CL2
Presumed ignition source
Not reported
Deflagration
N
High pressure explosion
N
High voltage explosion
N

References

Reference & weblink

Event description in the French database ARIA<br />
https://www.aria.developpement-durable.gouv.fr/accident/22101_en/?lang=… />
(accessed October 2020)<br />

JRC assessment