Event

Event ID
221
Quality
Description
A leak developed on a CGH2 tube trailer on the pigtail of one of the tube. The pigtail was cracked, possibly due to vibration. This trailer was tested the day before this incident and was found to be leak free.

The trailer consisted of 10 tube, and each tube has a pigitail. Trailers are tested for leaks every fill.
Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
Leak No Ignition (No additional details provided)
Macro-region
North America
Country
United States
Date
Main component involved?
Piping (Pigtail)
How was it involved?
Rupture
Initiating cause
Loss Of Tightness (Road Vibrations)
Root causes
Root CAUSE analysis
The INITIATING CAUSE was the cracking of a pigtail, probably mechanical vibration from the road.
Different degradation modes could be excluded, because trailer components are tested for leak by every filling.
A possible ROOT CAUSE could be a shortcoming in the design, but also a non-further understood generic material failure.

Facility

Application
Hydrogen Transport And Distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
Hydrogen Transport (No additional details provided)
All components affected
Hose
Location type
Open
Operational condition
Pre-event occurrences
The PHMSA report does not specify when the leak occurred. It is plausible to assume that it occurred when travelling or at the place of delivery.
Description of the facility/unit/process/substances
The trailer was a 10-tube trailer. Each tube had a capacity of almost 30 kg. Each tube had a pigtail attached to a main manifold.

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Environmental damage
0
Currency
US$
Property loss (onsite)
115
Property loss (offsite)
0
Post-event summary
The content of one tube was lost (approximately 30 kg). Material loss amounted to 115 US$.
Emergency action
The interstate highway was closed and nearby homes and businesses were evacuated.

Lesson Learnt

Corrective Measures
The trailer manufacturer investigated a changed of design, by adding additional support to the main manifold, to reduce the amount of vibration to the pigtail. If this improvement was eventually implemented, is not reported.

Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Released amount
29.4 kg
Presumed ignition source
No ignition

References

Reference & weblink

Incident I-1990060084 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: <br />
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%… />
(accessed September 2024)

JRC assessment