Event

Event ID
167
Quality
Description
Fire on a filter of an autoclave.
The event occurred in a plant for the production of plastics. After catalytic synthesis of amines, the filter of the autoclave was taken out for cleaning. During the removal, the fire started.
The fire was extinguished with water jets and water injection into the reactor vessel. The damages were very limited.

The event was caused by the presence of hydrogen at the top of the reactor, which was also in contact with the filter because the valve aiming at isolation the filter had remained open. The ignition of the hydrogen was probably due to the presence of the catalyst, which is pyrophoric when dry.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Fire (No additional details provided)
Macro-region
Europe
Country
France
Date
Main component involved?
Valve (Shut-Off)
How was it involved?
Erroneous Release & Formation Of A Flammable H2-Air Mixture
Initiating cause
Wrong Operation
Root causes
Root CAUSE analysis
The INITIATING cause was the presence of hydrogen in the filter. The intermediate cause is the failing to close the valve supposed to isolate the filter from the content of the reactor.
A CONTRIBUTING OR ROOT CAUSE reported was related to the procedure in place to prepare the filter for dismantling: it must be cleaned-up under water and then dried under nitrogen, to avoid the too intensive drying of the catalyst which can cause the production of sparks. In that case, the drying by nitrogen purging was longer than foreseen.

Facility

Application
Chemical Industry
Sub-application
Plastics production
Hydrogen supply chain stage
All components affected
,valve, filter, autoclave for the synthesis of plastic
Location type
Unknown
Location description
Industrial Area
Operational condition
Pre-event occurrences
After catalytic synthesis of an amine, the filter the autoclave was taken out for cleaning.

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
Only the filter's valve and manometer were damaged.
Emergency action
The site’s internal emergency plan was initiated.
The storage facility was located just 20 m from a 400 kV high-voltage power line. The use of hydraulic means was therefore impossible. Firefighters were able to close the hydrogen supply valve, which stopped the leak. The alert was called off at 2 a.m. The two skids impacted by the fire were removed from service.

Lesson Learnt

Corrective Measures
The following actions were taken:
1) reduction of the phase of drying of the catalyst by nitrogen;
2) maintaining the filter continuously under water during the dismantling;
3) emptying all the spaces containing the catalyst;
4) installing a hydraulic safe-guard for the case that the isolation valve does not function;
5) re-training personnel on the procedural instructions.

Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Presumed ignition source
Catalytic reaction

References

Reference & weblink

Event no. 25991 of the French database ARIA (accessed December 2020)