Explosion on the pressure release device of a hydrogen supply unit

Event

Event ID
142
Quality
Description
The explosion followed a hydrogen leak on a unit conditioning hydrogen.
The accident was caused by the mechanical rupture of a pressure regulator diaphragm on a section of a hydrogen line that included the dual-stage regulator, shut-off valves, and connecting flanges.This section of the hydrogen line had the purpose to reduce the hydrogen pressure from 220 to 50 bars and further to 3 bar and to supply it to an area for the conditioning of semi-trailers.
The fire was extinguished by powder-based fire estiguishers and by stopping the supply of hydrogen. FInally, the nitrogen was injected in the system..
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Main component involved?
Pressure Regulator
How was it involved?
Rupture & Formation Of A Flammable H2-Air Mixture
Initiating cause
Material Degradation (Generic)
Root causes
Unknown (No additional details provided)
Root CAUSE analysis
The INITIATING CAUSE was the mechanical failure of a pressure reduction device.
The ROOT CAUSE is unknown.

Facility

Application
Hydrogen Production
Sub-application
Production of industrial gases
Hydrogen supply chain stage
All components affected
hydrogen supply line, pressure reducer, hydrogen conditioning unit
Location type
Open
Location description
Industrial Area
Operational condition

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Environmental damage
0
Property loss (onsite)
0
Property loss (offsite)
0
Post-event summary
The damage was confined to the pressure reduction unit of the hydrogen line, on a ground surface of 4 m².

Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Actual pressure (MPa)
22
Presumed ignition source
Not reported

References

Reference & weblink

Event description in the French database ARIA<br />
https://www.aria.developpement-durable.gouv.fr/accident/28007/<br />
(accessed October 2020)