Event
- Event ID
- 893
- Quality
- Description
- During a patrol, an operator detects a hydrogen leak in a refinery on a footbridge 30 meters high. The origin of the leak is identified 4 days later on a pipe under insulation. The operator proceeds to remove the insulation (under SCBA). The leak is located at the level of a reinforcing saddle.
The installation is shut down and put under nitrogen. Thickness measurements and radiographic checks are used to characterise the nature of the crack defect. A leak sealing system (SOFM) is put in place while awaiting the removal of the pipework for assessment during the next shutdown. - Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- Leak No Ignition (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Root causes
- Root CAUSE analysis
- The INITIATING cause of the leak was a crack defect on the reinforcing saddle of a hydrogen pipe.
No detailed is known on the failure mechanism.
Facility
- Application
- Petrochemical Industry
- Sub-application
- Generic refinery process
- Hydrogen supply chain stage
- All components affected
- hydrogen pipeline
- Location type
- Open
- Location description
- Industrial Area
- Operational condition
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Presumed ignition source
- No ignition
References
- Reference & weblink
ARIA event no. 55163
JRC assessment
- Sources categories
- ARIA