Event
- Event ID
- 930
- Quality
- Description
- A leak occurred on a rack containing 12 cylinders of hydrogen (50 l at 200 bar each) delivered by a lorry inside the fenced storage area of a bulb manufacturing plant.
The plant’s safety manager closed access to the area, had the other lorry drivers on the site cut off their ignitions, and made them evacuate. The firefighters tested the air with an explosimeter and stopped the leak by closing the gate valve located on the outside of the rack. The valve was used to transfer hydrogen from the cylinders to their points of use.
The rack had been delivered by a crane lorry. Each of the top four corners of the rack was fitted with a steel ring that was used to lift the rack off the lorry. The gate valve was opened when one of the four lifting chains used to lift the rack off the lorry accidentally wrapped around it. - Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- Leak No Ignition (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Main component involved?
- Valve (Shut-Off)
- How was it involved?
- Leak & Formation Of A Flammable H2-Air Mixture
- Initiating cause
- Impact, Rollover, Crash
- Root causes
- Root CAUSE analysis
- INITIATING cause was the accidental opening of the main hydrogen valve during unloading of the lorry.
Facility
- Application
- Hydrogen Transport And Distribution
- Sub-application
- CGH2 cylinders truck
- Hydrogen supply chain stage
- Hydrogen Transport (No additional details provided)
- All components affected
- cylinders
- Location type
- Open
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- The lorry had been delivered to destination and the unloading of the rack of hydrogen cylinders was ongoing by means of the lorry crane
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Post-event summary
- The ARIA report (see references) does not provide quantitative assessment of the amount of hydrogen released.
Lesson Learnt
- Corrective Measures
According to the ARIA report (see references), the operator took the following two corrective measures:
i) stopped deliveries of this type of rack ,
ii) replaced it by one with 16 cylinders, fitted with a cover and a central lifting ring.
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Actual pressure (MPa)
- 20
- Design pressure (MPa)
- 20
- Presumed ignition source
- No ignition
References
- Reference & weblink
Event description in the French database ARIA<br />
https://www.aria.developpement-durable.gouv.fr/accident/44315/<br />
(accessed September 2020)<br />
JRC assessment
- Sources categories
- ARIA