Release from hydrogen cylinders storage of a chemical plant

Event

Event ID
930
Quality
Description
A leak occurred on a rack containing 12 cylinders of hydrogen (50 l at 200 bar each) delivered by a lorry inside the fenced storage area of a bulb manufacturing plant.

The plant’s safety manager closed access to the area, had the other lorry drivers on the site cut off their ignitions, and made them evacuate. The firefighters tested the air with an explosimeter and stopped the leak by closing the gate valve located on the outside of the rack. The valve was used to transfer hydrogen from the cylinders to their points of use.

The rack had been delivered by a crane lorry. Each of the top four corners of the rack was fitted with a steel ring that was used to lift the rack off the lorry. The gate valve was opened when one of the four lifting chains used to lift the rack off the lorry accidentally wrapped around it.
Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
Leak No Ignition (No additional details provided)
Macro-region
Europe
Country
France
Date
Main component involved?
Valve (Shut-Off)
How was it involved?
Leak & Formation Of A Flammable H2-Air Mixture
Initiating cause
Impact, Rollover, Crash
Root causes
Root CAUSE analysis
INITIATING cause was the accidental opening of the main hydrogen valve during unloading of the lorry.

Facility

Application
Hydrogen Transport And Distribution
Sub-application
CGH2 cylinders truck
Hydrogen supply chain stage
Hydrogen Transport (No additional details provided)
All components affected
cylinders
Location type
Open
Location description
Industrial Area
Operational condition
Pre-event occurrences
The lorry had been delivered to destination and the unloading of the rack of hydrogen cylinders was ongoing by means of the lorry crane

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
The ARIA report (see references) does not provide quantitative assessment of the amount of hydrogen released.

Lesson Learnt

Corrective Measures

According to the ARIA report (see references), the operator took the following two corrective measures:
i) stopped deliveries of this type of rack ,
ii) replaced it by one with 16 cylinders, fitted with a cover and a central lifting ring.


Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Actual pressure (MPa)
20
Design pressure (MPa)
20
Presumed ignition source
No ignition

References

Reference & weblink

Event description in the French database ARIA<br />
https://www.aria.developpement-durable.gouv.fr/accident/44315/<br />
(accessed September 2020)<br />

JRC assessment