Description
A leak occurred on a line connecting the hot separator to the cold separator of a refinery diesel desulphurization.
The alert was given by the activation of the fixed H2S detector.
The 30 bar pressure line contained essentially hydrogen with a high concentration of H2S. The operators stopped the unit and isolated the leak in about ten minutes. The line was pierced at a bend at 135 ° C following a bend at 90 ° C. The accident investigation showed that the presence of the elbows resulted in turbulence which created a localized depression: this configuration favoured the formation of deposits (in particular during the stops of the water wash pump). Deposition corrosion developed until the line was punctured. A 90 ° elbow inspection was performed by the site inspection department but not at 135 ° C.
Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
Leak No Ignition (No additional details provided)
Macro-region
Europe
Country
France
Date
Root causes
Root CAUSE analysis
Localised corrosion in pipe elbows, until the line was punctured.

Facility

Application
Petrochemical Industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected
process gas pipe
Location type
Unknown
Location description
Industrial Area
Operational condition

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
The operators stopped the unit and isolated the leak in about ten minutes.

Event Nature

Release type
gas mixture
Involved substances (% vol)
H2,
H2S
Design pressure (MPa)
3
Presumed ignition source
No ignition