LH2 tanker venting on a highway

Event

Event ID
1186
Quality
Description
A liquid hydrogen tanker (with a water capacity of 2000 l) was passing a highway interchange, when the safety valve of the tank activated, releasing hydrogen gas. The drivers stopped first on the shoulder of the road near the junction for inspection. Then he moved to a service area for safety reasons. They performed a controlled release of the whole tank content, after having create a safety area around the tanker.
The probable cause of the valve activation was the increase of the internal pressure of the tank, due to the loss of thermal insulation provided by the vacuum between the two tank shells. The road vibrations had induced cyclic stress to the welded joint of the piping that penetrates from the inner container to the outer container. The welding failed to o fatigue, allowing hydrogen entering the vacuum layer between the inner \and the outer shell. With the vacuum deteriorating, its thermal insulation capacity faded as well with consequent temperature and pressure rise beyond the activation set point of the safety valve.
According to the inspection records, the tank had not been inspected at the legally prescribed inspection interval. Furthermore, the filling stations were filling the tanks without checking whether they had been properly and timely inspected.

[Note of HIAD validator: the KHK record provides a second cause. It is not known if these are two hypotheses to explain the loss of thermal insulations, or two different failures. “One of the plate fixing the inner shell of the tank inside the outer container broke due to fatigue, causing the inner shell to fall off inside the outer shell”.]
Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
Leak No Ignition (No additional details provided)
Macro-region
Asia
Country
Japan
Date
Main component involved?
Prd (Valve)
How was it involved?
Correct Activation
Initiating cause
Over-Pressurisation (Thermal Insulation Degradation)
Root causes
Root CAUSE analysis
The INITIATING was the damage caused by road vibration to the welds of internal structures of the cryogenic tank, with consequent reduction or complete loss of its thermal insulation capacity.
The ROOT CAUSE was the lack of correct inspection and control. Probably also the original welds had not been designed to survive prolonged vibrations as those from roads travelling.

Facility

Application
Hydrogen Transport And Distribution
Sub-application
LH2 tanker
Hydrogen supply chain stage
Hydrogen Transport (No additional details provided)
All components affected
safety valve, vacuum shell
Location type
Open
Operational condition
Pre-event occurrences
The report mentions that the cryogenic tank had been first filled and then loaded on the truck.

Description of the facility/unit/process/substances
DESCRIPTION OF THE UNIT
This detail suggests a non-permanently installed tank. The value of only 2000 l of liquid hydrogen (only 100 kg) confirms that this was not really a LH2 tanker, but a smaller cryogenic vessel.

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0

Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Presumed ignition source
No ignition

References

Reference & weblink

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): <br />
https://www.khk.or.jp/public_information/incident_investigation/hpg_inc… />
(accessed May 2025)