Description
The fire took place during maintenance works in one out of the three gas extractors of the coke process line. Main cause was displacement of a flange which allowed the entrance of flammable mixture gas (methane, carbon monoxide hydrogen and benzene) which ignited probably due to electrostatic spark.
According to the ARIA report (see references) total quantity of gas released was 62 400 m³, consisting of 11,7 t CH4, 0,98 t C6H6, 5,1 t CO and 3,4 t H2.

During maintenance works, gas extractors were usually isolated and kept under continuous flow of N2. However, in this case, N2 pressure seemed to be not enough to avoid the entrance of flammable gas.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Fire (No additional details provided)
Macro-region
Europe
Country
France
Date
Root causes
Root CAUSE analysis
INITIATING cause was probably the inert gas pressure insufficient to prevent the entrance of the flammable mixture.

Facility

Application
Steel And Metals Industry
Sub-application
Steel manufacturing
Hydrogen supply chain stage
All components affected
coke process line, flange
Location type
Unknown
Location description
Industrial Area
Operational condition
Pre-event occurrences
The event took place during maintenance of a gas extractor, which has a diameter of 1400 mm. During maintenance, the line was isolated from gas stream using two flanges, one before and another one after the equipment.
The accident occurred after maintenance works have finished and the gas extractor was been prepared again for operation: the procedure required as final steps the closing of the downstream flange and then the opening of the inlet one. The leak occurred immediately after the opening of the inlet flange.

Emergency & Consequences

Number of injured persons
2
Number of fatalities
0
Post-event summary
Damage to property: on-site more than 2 millions of Euros, off-site more than 0.5M millions of Euros.

Lesson Learnt

Corrective Measures

The operator has foreseen to improve the procedure for the isolation of the section at the following maintenance and to review the risk assessment.

Event Nature

Release type
gas mixture
Involved substances (% vol)
H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t
Released amount
H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t
Presumed ignition source
Not reported
Flame type
Other

References

Reference & weblink

Event description in the European database eMARS<br />
https://emars.jrc.ec.europa.eu/en/eMARS/accident/view/2c958f15-e9a3-11e… />
(accessed September 2020)<br />

Radio RPA online news: <br />
https://www.radiorpa.fr/fuite-de-gaz-enflamm%C3%A9e-2-bless%C3%A9s-%C3%… />
(accessed July 2024)

Online news Le Port de Saint Louis: company communication

ARIA incident No. 1706

JRC assessment