Event
- Event ID
- 937
- Quality
- Description
- The fire took place during maintenance works in one out of the three gas extractors of the coke process line. Main cause was displacement of a flange which allowed the entrance of flammable mixture gas (methane, carbon monoxide hydrogen and benzene) which ignited probably due to electrostatic spark.
According to the ARIA report (see references) total quantity of gas released was 62 400 m³, consisting of 11,7 t CH4, 0,98 t C6H6, 5,1 t CO and 3,4 t H2.
During maintenance works, gas extractors were usually isolated and kept under continuous flow of N2. However, in this case, N2 pressure seemed to be not enough to avoid the entrance of flammable gas. - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Fire (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Root causes
- Root CAUSE analysis
- INITIATING cause was probably the inert gas pressure insufficient to prevent the entrance of the flammable mixture.
Facility
- Application
- Steel And Metals Industry
- Sub-application
- Steel manufacturing
- Hydrogen supply chain stage
- All components affected
- coke process line, flange
- Location type
- Unknown
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- The event took place during maintenance of a gas extractor, which has a diameter of 1400 mm. During maintenance, the line was isolated from gas stream using two flanges, one before and another one after the equipment.
The accident occurred after maintenance works have finished and the gas extractor was been prepared again for operation: the procedure required as final steps the closing of the downstream flange and then the opening of the inlet one. The leak occurred immediately after the opening of the inlet flange.
Emergency & Consequences
- Number of injured persons
- 2
- Number of fatalities
- 0
- Post-event summary
- Damage to property: on-site more than 2 millions of Euros, off-site more than 0.5M millions of Euros.
Lesson Learnt
- Corrective Measures
The operator has foreseen to improve the procedure for the isolation of the section at the following maintenance and to review the risk assessment.
Event Nature
- Release type
- gas mixture
- Involved substances (% vol)
- H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t - Released amount
- H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t - Presumed ignition source
- Not reported
- Flame type
- Other
References
- Reference & weblink
Event description in the European database eMARS<br />
https://emars.jrc.ec.europa.eu/en/eMARS/accident/view/2c958f15-e9a3-11e… />
(accessed September 2020)<br />Radio RPA online news: <br />
https://www.radiorpa.fr/fuite-de-gaz-enflamm%C3%A9e-2-bless%C3%A9s-%C3%… />
(accessed July 2024)Online news Le Port de Saint Louis: company communication
ARIA incident No. 1706
JRC assessment
- Sources categories
- eMARS