In a petrochemical plant, a gas mixture at 270 bar made of 75% hydrogen (H2) and 25% methane (CH4) leaked through the bottom valve of a dryer of a resin production unit.
After detection of the leak, the explosive zone near the equipment was estimated to be 7 m. Hydrogen sulphide (H2S) was detected around the leak. The installation was shutdown and depressurised, a nitrogen injection used to neutralise the gas mixture.
The emergency plan was called at 13:35, and terminated at 16:40. The pressure in the dryer had dropped to 34 bar.
Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
Leak No Ignition (No additional details provided)
Macro-region
Europe
Country
France
Date
Root causes
Unknown (No additional details provided)

Facility

Application
Chemical Industry
Sub-application
Resins production
Hydrogen supply chain stage
All components affected
valve, dryer, a resin production unit
Location type
Open
Location description
Industrial Area
Operational condition

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
No ignition.

Event Nature

Release type
gas mixture
Involved substances (% vol)
H2 75%,
CH4 25%
Presumed ignition source
No ignition

References

Reference & weblink

ARIA data base <br />
event no. 43855

JRC assessment