Event
- Event ID
- 167
- Quality
- Description
- Fire on a filter of an autoclave.
The event occurred in a plant for the production of plastics. After catalytic synthesis of amines, the filter of the autoclave was taken out for cleaning. During the removal, the fire started.
The fire was extinguished with water jets and water injection into the reactor vessel. The damages were very limited.
The event was caused by the presence of hydrogen at the top of the reactor, which was also in contact with the filter because the valve aiming at isolation the filter had remained open. The ignition of the hydrogen was probably due to the presence of the catalyst, which is pyrophoric when dry. - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Fire (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Main component involved?
- Valve (Shut-Off)
- How was it involved?
- Erroneous Release & Formation Of A Flammable H2-Air Mixture
- Initiating cause
- Wrong Operation
- Root causes
- Root CAUSE analysis
- The INITIATING cause was the presence of hydrogen in the filter. The intermediate cause is the failing to close the valve supposed to isolate the filter from the content of the reactor.
A CONTRIBUTING OR ROOT CAUSE reported was related to the procedure in place to prepare the filter for dismantling: it must be cleaned-up under water and then dried under nitrogen, to avoid the too intensive drying of the catalyst which can cause the production of sparks. In that case, the drying by nitrogen purging was longer than foreseen.
Facility
- Application
- Chemical Industry
- Sub-application
- Plastics production
- Hydrogen supply chain stage
- All components affected
- ,valve, filter, autoclave for the synthesis of plastic
- Location type
- Unknown
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- After catalytic synthesis of an amine, the filter the autoclave was taken out for cleaning.
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Post-event summary
- Only the filter's valve and manometer were damaged.
- Emergency action
- The site’s internal emergency plan was initiated.
The storage facility was located just 20 m from a 400 kV high-voltage power line. The use of hydraulic means was therefore impossible. Firefighters were able to close the hydrogen supply valve, which stopped the leak. The alert was called off at 2 a.m. The two skids impacted by the fire were removed from service.
Lesson Learnt
- Corrective Measures
- The following actions were taken:
1) reduction of the phase of drying of the catalyst by nitrogen;
2) maintaining the filter continuously under water during the dismantling;
3) emptying all the spaces containing the catalyst;
4) installing a hydraulic safe-guard for the case that the isolation valve does not function;
5) re-training personnel on the procedural instructions.
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Presumed ignition source
- Catalytic reaction
References
- Reference & weblink
Event no. 25991 of the French database ARIA (accessed December 2020)