A fire in the hydrotreatment oven of a refinery

Event

Event ID
103
Quality
Description
An explosion, followed by a fire, happened in an oven belonging to the hydro-treatment unit. Following a shutdown, the tube, containing only gaseous products and hydrogen, had been affected by instable flows. In presence of a flows lower than nominal, the tube temperature raised up to its mechanical resistance limit. Under internal pressure, it failed with a longitudinal crack of ca. 750 mm
The unit was shut down and the fire extinguished by itself.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Main component involved?
Pipe
How was it involved?
Rupture & Formation Of A Flammable H2-Hc-Air Mixture
Initiating cause
Over-Heating (Wrong Operation)
Root causes
Root CAUSE analysis
The INITIATING CAUSE was the failure of a tube of the oven due to overheating.

The the destabilisation of the operative conditions was due to shortcoming in the capacity to control the operative parameters, also due to lack of effective diagnostics by means of measuring gauges.

Facility

Application
Petrochemical Industry
Sub-application
hydrotreatment
Hydrogen supply chain stage
All components affected
Hydrotreatment unit
Location type
Unknown
Location description
Industrial Area
Operational condition
Pre-event occurrences
The oven used for hydrotreatment of complex oils had been shut down 3 hours before.
Description of the facility/unit/process/substances
It is probable that the oven affected by the explosion was a heat exchanger used to pre-heat hydrogen and other process gases before entering he hydro-treatment reactor.

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
As a maintenance was planned in January 2006, the unit will not restart before this date.
Official legal action
The unit could not restart before the conclusions of investigation and the subsequent updating of safety measures.

Lesson Learnt

Corrective Measures

The plant operator:
1) verified the soundness of the range of allowed operative conditions,
2) ensured the correct functioning of the thermocouples measuring the temperature of the tubes,
3) improved the operative procedures, in particular those regulating the transitory phases.

Event Nature

Release type
gas
Involved substances (% vol)
H2 (mainly)
Presumed ignition source