Skip to main content
Clean Hydrogen Partnership

Fire in hydrogenation unit of a monomer production plant

Event

Event ID
785
Quality
Description
The fire was in a polyamide production chemical plant classified SEVESO

During maintenance of an isolated unit producing a polyamide monomer (LACTAME), a fire developed on the ground floor of the unit of hydrogenation of cyclo-dodecadiene (CDA).
A fire detector on the unit triggered an alarm 4 min after the fire started and the station operator put the unit in safe conditions and alerted the firefighters of the site. The fire was controlled after a half an hour. The nitrogen purging device of the reactors was put into service, it then presented malfunctions: difficulties of connection of the hose, leakage on the valve.
The unit was slightly damaged (damaged valves, melting cables), and it restarted 13 days later.

The analysis of the accident by the plant operator showed that a sensor had failed to give the signal of low level in the CDA storage tank. The low level has allowed hydrogen into the production line, which was in stand-by. The hydrogen escaped from the manual valve at the bottom of the reactor finishing the process . This valve had already been found leaking a week before and tightened.
In the presence of an unidentified ignition source, the leaked hydrogen ignited. The fire was further alimented by the opening of the valves of automatic degassing of the reactors, due fire damage. This opening caused the increase of the hydrogen supply of the unit. Late fire detection and too slow pressure drop in the decompression line were also aggravating factors.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Fire (No additional details provided)
Macro-region
Europe
Country
France
Date
Root causes
Root CAUSE analysis
INITIATING cause has been the failure of a low-level sensor, which has allowed the injection of hydrogen into the production line.

Facility

Application
Chemical Industry
Sub-application
Polyamide production
Hydrogen supply chain stage
All components affected
polyamide monomer unit, hydrogenation of cyclododecadiene unit
Location type
Semiconfined
Location description
Industrial Area
Operational condition
Pre-event occurrences
Occurred during maintenance

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
There were no impact on the environment.
Damage to the unit was limited to components such as valves, melting cables).
The plant restarted 13 days later.

Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Presumed ignition source
Not reported

References

Reference & weblink

ARIA data base <br />
event no. 38732

JRC assessment