Description
A leak occurred on a 4 inch hydrogen main gas line which ran along a pipe bridge at the east end of a first stage compression plant building. The relased hydrogen ignited.
The source of ignition was hot welding sparks arising from work being carried out by contract personnel whilst installing a new chlorine line above the hydrogen lineon the pipe-bridge.

Before the welding work was carried out, an explosivity test had been carried out in the area and a 0 explosive gas result had been reproted in the work permit.
An investigation into the incident found that the removed section of the hydrogen main revealed an elliptical hole 2 centimetres x 1 and a half centimetres. It was only when the lagging was disturbed that the hydrogen leak became obvious.The area around the hole in hydrogen main was very pitted suggesting that the failure was due to localised corrosion.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Fire (No additional details provided)
Macro-region
Europe
Country
United Kingdom
Date
Main component involved?
Pipe
How was it involved?
Leak & Formation Of A Flammable H2-Air Mixture
Initiating cause
Wrong Operation
Root causes
Root CAUSE analysis
The INITIATING CAUSE was an elliptical hole of 2 centimetres x 1.5 centimetres.
It was very probably due to localised corrosion.
The leak was not detected during the explosivity test because of a build up of scale sealing the hole, possibly dislodged later by the activities of the contractors in the area. The technical reason for the corrosion is not povided or known.
Neverhtless, ROOT CAUSE could be possibly attributed to a lack of effective inspection, not able to detect the progress of the corrosion.

Facility

Application
Chemical Industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected
Separation equipment
Location type
Unknown
Location description
Industrial Area
Operational condition
Pre-event occurrences
Welding works were ongoing, but the plant had not been shutdown (pesene of flammabe gases had been excluded by measures).

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0

Event Nature

Release type
gas
Involved substances (% vol)
H2 100%
Hole shape
Near Circular
Hole length (mm)
2
Hole width (mm)
1.5
Presumed ignition source
Welding
Deflagration
N
High pressure explosion
N
High voltage explosion
N
Flame type
Jet flame

References

Reference & weblink

JRC assessment