Event
- Event ID
- 791
- Quality
- Description
- The incident occurred at the power generator of a nuclear power plant, in a non-nuclear area of the plant. Although hydrogen was use in the system, it was not affected by the fire.
Oil leaked at a bearing seal between rotor and stator of an alternator. The ignition of the leaking oil, fed by a 60 m³ tank, caused the defect of the turbine and the automatic shutdown of the nuclear unit.
The operator started the emergency plan after 35 minutes and the departmental operational centre was alerted after 50 minutes. The engine room was evacuated and a security perimeter was set up.
The operator purged the hydrogen of the alternator cooling circuit. Public firefighters and the site fire team extinguished the fire around after approximately 1.5 hours by means of foam lances. This allowed to stop oil leak. - Event Initiating system
- Classification of the physical effects
- No Hydrogen Release
- Nature of the consequences
- Macro-region
- Europe
- Country
- France
- Date
- Root causes
- Root CAUSE analysis
- Oil leaked at a bearing seal between rotor and stator of an alternator in an uncontrolled area of a nuclear power plant. The ignition at 12:48 of the leak fed by a 60 m³ tank caused the defect of the turbine and the automatic shutdown of the nuclear unit.
Facility
- Application
- Power Plant
- Sub-application
- Nuclear power plant
- Hydrogen supply chain stage
- All components affected
- bearing seal, rotor and stator of an alternator, non-radioactive area
- Location type
- Confined
- Location description
- Industrial Area
- Operational condition
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Post-event summary
- automatic shutdown of the nuclear unit
Lesson Learnt
- Lesson Learnt
This is an incident with a conventional oil fire, in presence of a subsystem (hydrogen coolant of the alternator) which was not affected. It is the only HIAD incident, among those related to turbine-generator failures, which did not bring to hydrogen fire. Safety systems worked as expected.
Event Nature
- Release type
- Gas-liquid mixture
- Involved substances (% vol)
- H2,
oil - Presumed ignition source
- No release
References
- Reference & weblink
ARIA data base <br />
event no. 43981
JRC assessment
- Sources categories
- ARIA