Event
- Event ID
- 984
- Quality
- Description
- the fire was detected by an employee during the normal inspection tour. It was caused by the ignition of a leak of process gas (hydrogen, methane and water vapour) from the reforming furnaces.
The plant operator stopped the ammonia unit by manually triggering the safety emergency procedure. The natural gas supply was cut off, and this immediately extinguished the flame.
The nitric acid unit was kept running at minimum rate. The hot ammonium nitrate solution and ammonium nitrate units are shut down due to lack of ammonia.
The nitric acid production unit was restarted in the morning, the ammonium nitrate unit the following day.
(ARIA database) - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Fire (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Main component involved?
- Reactor / Oven / Furnace / Test Chamber
- How was it involved?
- Leak & Formation Of A Flammable H2-Ch4-Mixture
- Initiating cause
- Unknown
- Root causes
- Unknown (No additional details provided)
- Root CAUSE analysis
- The ARIA report does not provide any cause analysis. This incident is very similar to the one described in HIAD event 983, which occurred in the same plant in 2019.
Facility
- Application
- Chemical Industry
- Sub-application
- Fertilisers production
- Hydrogen supply chain stage
- All components affected
- reformer
- Location type
- Open
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- This incident is very similar to the one described in HIAD event 983, which occurred in the same plant in 2019.
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Post-event summary
- The only consequence was the temporary reduction of the production of ammonium nitrate (H₄NO₃) and fertilisers due to lack of ammonia.
Lesson Learnt
- Lesson Learnt
This incident is very similar to the one described in HIAD event 983, which occurred in the same plan in 2019. At that time, the leak had been found on a gasket, and all the gasket of the same furnace were replaced.
The description of the event in ARIA (see references) does not contain enough details to understand incident causes and deduce a lesson learnt. One general observation can be issued: despite the enormous progress achieved in safety records of hydrogen in industrial processes, attention to preventive measures is still required.
Event Nature
- Release type
- gas mixture (syngas)
- Involved substances (% vol)
- syngas
- Presumed ignition source
- Not reported
References
- Reference & weblink
Event description no 55060 in the French database ARIA (accessed October 2021)
JRC assessment
- Sources categories
- ARIA