Event
- Event ID
- 613
- Quality
- Description
- The explosion occurred during preparatory work to start a compressor that supplies hydrogen gas to a heavy oil direct desulfurization unit. The inspection cover of the crank case came off, injuring an operator.
Normally, nitrogen was supplied to purge the case , displacing the hydrogen leaking from the shaft seal of the compressor cylinder. The accident investigation revealed that the nitrogen flow meter was broken, causing almost no gas to flow.
It is assumed that the hydrogen leaking from the shaft seal of the cylinder entered the crankcase, ignited and burned due to static electricity. The expansion force of the explosion caused the inspection cover of the crankcase to fly off. - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Asia
- Country
- Japan
- Date
- Main component involved?
- Compressor / Booster / Pump (Piston)
- How was it involved?
- Internal Explosion (H2-Air Mixture)
- Initiating cause
- Inadequate Or No Purge
- Root causes
- Root CAUSE analysis
- The INITIATING CAUSE was the failing of the nitrogen system supposed to purge the compressor crankcase free of hydrogen.
The failure to purge was due to a broken flow metre which was indicating nitrogen flow while almost no nitrogen was flowing
The ROOT CAUSE was a lack of proper inspection and maintenance.
Facility
- Application
- Petrochemical Industry
- Sub-application
- Hydrodesulphurisation process
- Hydrogen supply chain stage
- Hydrogen Compression (No additional details provided)
- All components affected
- flow meter, shaft seal,
compressor cylinder,
crankcase,
H2 compressor - Location type
- Unknown
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- Preparatory operation was ongoing for the start of a hydrogen compressor
Emergency & Consequences
- Number of injured persons
- 1
- Number of fatalities
- 0
- Post-event summary
- minor injury
Lesson Learnt
- Lesson Learnt
This is an incident cause by the wrong indication of an instrument, which was a critical component of preventing measures of the system. Special attention should be given to the proper functioning of components critical to safety. Effective check/inspection shall be in place to detect early enough malfunctioning. Moreover, redundancy could be provided, for example by installing two components with the same function.
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Presumed ignition source
- Static electricity
References
- Reference & weblink
High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): <br />
https://www.khk.or.jp/public_information/incident_investigation/hpg_inc… />
(accessed May 2025)The first entry in HIAD was coming from RISCAD, which is now closed.<br />
JRC assessment
- Sources categories
- KHK