Event
- Event ID
- 1065
- Quality
- Description
- A fire broke out on the insulating plastic elements of an alkaline electrolyser in a unit of a chemical plant. The shift saw the smoke from the control room.
The first action was to drain the potash into a tank provided for this purpose and to shut down the electrolyser. The on-call electrician interrupted the electricity.
The safety technician brought the fire under control in less than 10 minutes using CO2 extinguishers. After approximately six hours, the unit was restarted. - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Fire (No additional details provided)
- Macro-region
- Europe
- Country
- France
- Date
- Main component involved?
- Electrolytic Cell
- How was it involved?
- Fire
- Initiating cause
- Malfunctioning (Electrolyser, Cross-Over)
- Root causes
- Unknown (No additional details provided)
- Root CAUSE analysis
- The INITIATING CAUSE of the event was potash leak on the electrolyser block that induced an electric arc between the electric block and the bus bar. This ignition caused a rise in temperature followed by the outbreak of fire.
ROOT CAUSE unknown.
Facility
- Application
- Hydrogen Production
- Sub-application
- water electrolysis
- Hydrogen supply chain stage
- All components affected
- Alkaline electrolyser
- Location type
- Unknown
- Operational condition
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 0
- Environmental damage
- 0
- Property loss (onsite)
- 0
- Property loss (offsite)
- 0
Lesson Learnt
- Corrective Measures
Following the event, the operator implemented the following actions:
• Increase the frequency of predictive and preventive maintenance: preventive visit to each electrolyser with cleaning or repair if necessary;
• Add to the return of experience the occurrence of this event;
• Increase operator awareness.
Event Nature
- Release type
- liquid
- Involved substances (% vol)
- KOH (solution)
- Presumed ignition source
- Not reported
References
- Reference & weblink
ARIA event<br />
https://www.aria.developpement-durable.gouv.fr/accident/59900/
JRC assessment
- Sources categories
- ARIA