Event
- Event ID
- 343
- Quality
- Description
- Two men had decided to fill a weather balloon with hydrogen in a storeroom located in the basement of a block of flats. Their idea was to attach a video camera to the balloon for the purpose of taking aerial photos. To fill in the balloon, the men had purchased a 20 kg hydrogen bottle and a valve and constructed a special mouthpiece for the purpose. They had tried filling a similar balloon previously. Then, they did not experience any problems in filling the balloon and had left the balloon in the basement to let it empty.
Before filling the balloon, they had opened all the vents in the basement. When the balloon had inflated to a diameter of about one metre, it suddenly exploded. A woman and two children were also present in the room during the fill-up. All those present sustained burns in the explosion.
The explosion damaged the block of flats in several ways: the main entrance door was torn off, nearly all of the doors and fire doors along the corridor cutting across the building basement were damaged, and one of the masonry partition walls fell down. - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Europe
- Country
- Finland
- Date
- Main component involved?
- Balloon
- How was it involved?
- Explosion (H2-Air Mixture)
- Initiating cause
- Wrong Operation
- Root causes
- Root CAUSE analysis
- INITIATING CAUSE: It is highly probable that the hydrogen was still present in the room after having emptied previously a balloon, and that the hydrogen ignited by an electrostatic charge.
ROOT CAUSE: the men were aware of the risks associated with hydrogen, and been informed that it is not permitted to fill up a balloon in a basement storeroom. Nevertheless they decided to proceed.
Facility
- Application
- Other
- Sub-application
- weather balloons
- Hydrogen supply chain stage
- All components affected
- Build environment, hydrogen balloon
- Location type
- Confined
- Operational condition
- Pre-event occurrences
- Abnormal condition because the filling of the balloon occurred in not fit-for-purpose environment and by not-experts.
Emergency & Consequences
- Number of injured persons
- 4
- Number of fatalities
- 0
- Post-event summary
- A woman and two children were also present in the room during the fill-up. All those present sustained burns in the explosion.
The explosion damaged the block of flats in several ways: the main entrance door was torn off, nearly all of the doors and fire doors along the corridor cutting across the building basement were damaged, and one of the masonry partition walls fell down.
Lesson Learnt
- Corrective Measures
- The two men were informed of the fact that their action was illegal.
Event Nature
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Presumed ignition source
- Static electricity
- Ignition delay
- 0
- Deflagration
- N
- High pressure explosion
- Y
- High voltage explosion
- N
References
- Reference & weblink
Source lost
JRC assessment
- Sources categories
- Unknown