Event
- Event ID
- 1075
- Quality
- Description
- A lightning strike caused a voltage drop on the power supply of a chlorine-alkali plant using the mercury process. The emergency electrical system was activated, though restoring the external supply voltage in less than 200 ms rendered the entire system inconsistent; some units were operating normally, but all units connected to the emergency devices (including the mercury pump) remained idle.
An explosive mix of 500 kg of chlorine and an unknown amount of hydrogen accumulated inside the low-pressure chlorine treatment circuit. When the mix exploded, it injured two employees and destroyed the whole circuit (damage: 237 000 euros). - Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Europe
- Country
- Germany
- Date
- Main component involved?
- Electrolytic Cell
- How was it involved?
- Internal Explosion (H2-Cl2 Mixture)
- Initiating cause
- Extreme Environmental Conditions (Lightning)
- Root causes
- Root CAUSE analysis
- The INITIATING cause was the loss of power due to lightning. The power recovery system was not considering that several components would have not properly reacted to micro-losses.
Facility
- Application
- Chemical Industry
- Sub-application
- Chlorine production
- Hydrogen supply chain stage
- All components affected
- mercury pump
- Location type
- Confined
- Location description
- Industrial Area
- Operational condition
- Pre-event occurrences
- because of a lightning, a power loss had occurred, followed by the activation of the emergency electrical system.
Emergency & Consequences
- Number of injured persons
- 0
- Number of fatalities
- 2
- Currency
- Euro
- Property loss (onsite)
- 237000
- Post-event summary
- Two employees injured and the whole electrolyser circuit destroyed.
Lesson Learnt
- Lesson Learnt
- :
According to ARIA, tis accident demonstrated the need to improve the simple binary approach (i.e. on/off) in term of power availability. It is necessary to incorporate short-duration voltage drops (electrical disturbances) into the safety reports.
An installation's emergency power supply must be designed by integrating a SIL 2 safety integrity level (according to the Standards IEC 61508 / 61511). - Corrective Measures
The site operator extended personnel training modules to include the facility's operating details, in a step to better cope with unidentified defects.
Event Nature
- Release type
- gas mixture
- Involved substances (% vol)
- H2,
Cl2 - Presumed ignition source
- Weather - lightning
References
- Reference & weblink
ARIA event<br />
https://www.aria.developpement-durable.gouv.fr/accident/40197/<br />
(accessed July 2023)ARIA full report <br />
https://www.aria.developpement-durable.gouv.fr/accident/40197/<br />
(accessed July 2023)Event from German database ZEMA<br />
https://www.infosis.uba.de/index.php/de/site/2854/zema/index/16137.html… />
(accessed December 2024)
JRC assessment
- Sources categories
- ARIA