Explosion and fire in a fertiliser production plant

Event

Event ID
949
Quality
Description
A syngas leak (hydrogen + methane) occurred at exit of the ammonia production reactor and led to an explosion followed by a fire.
The start point of the sequence of events was the syngas at the reactor outlet reaching an abnormal pressure of 150 bar and a temperature of 300°C. This caused a flange seal to move, causing the gases to leak.
The accident caused a pressure waves and fire observed on the installations over a distance of 450 metres.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
Slovakia
Date
Root causes
Root CAUSE analysis
The INITIATING cause was an overpressure on a flange, causing its loss of confinement. The sources do not mention the reason(s) for the unexpectedly high-pressure value, but it could be assumed that it was an exceptional event, but not completely unexpected.

From the corrective actions adopted it appears an absence of a risk assessment based on the possibility of ignition of flammable gases at the ammonia reactor, the usage of a inadequate components (flange) and the lack of effective communication of an alarm to personnel. These points hint at ROOT CAUSES related to inadequate (safety) design and risk management.

Facility

Application
Chemical Industry
Sub-application
Fertilisers production
Hydrogen supply chain stage
All components affected
ammonia reactor
Location type
Open
Location description
Industrial Area
Operational condition
Description of the facility/unit/process/substances
DESCRIPTION OF THE COMPONENTS
The pipe diameter at the exit of the ammonia reactor had a diameter of 300 mm (DN300). The flange used on this pipe was a model with a lenticular seal between the clamp and the tube, screwed to the flange by bolts.

Emergency & Consequences

Number of injured persons
5
Number of fatalities
0
Currency
Euros
Property loss (onsite)
12000000
Property loss (offsite)
0
Post-event summary
The accident caused 5 injuries. Material damage due to the pressure waves and fire was observed on the installations over a distance of 450 metres. The consequences for the site were estimated at €12,000,000.

Lesson Learnt

Corrective Measures

After the accident, the operator considered the following measures:
1) to conduct an explosion risk study in areas where ammonia or flammable gases are handled and in areas where an explosion has already occurred;
2) the installation of an personnel alert system and an evacuation procedure in the event of a process failure that could lead to an explosion;
3) the replacement of the flanges by a model more adapted to over-pressure hazard.

Event Nature

Release type
gas mixture (syngas)
Involved substances (% vol)
syngas
Release duration
unknown
Actual pressure (MPa)
15
Design pressure (MPa)
< 15
Presumed ignition source
Not reported

References

Reference & weblink

Event description in the French database ARIA<br />
https://www.aria.developpement-durable.gouv.fr/accident/50265/<br />
(accessed October 2020)<br />

Event description in the European database eMARS<br />
https://emars.jrc.ec.europa.eu/en/emars/accident/view/f8c4af35-d462-cb6… />
(accessed October 2025)<br />

JRC assessment