Explosion and fire in a fertiliser plant

Event

Event ID
196
Quality
Description
The explosion occurred in the compressors unit of the plant. Witnesses reported a cloud of yellow smoke and a fire ball at its bottom.
This first event was followed by a fire fed by a hydrogen pipe (5.5 t of hydrogen was present in the system). The fire brigade confined it until its natural extinction.

A negligible amount of ammonia was probably released to the environment. No injured but a considerable materials damage: the plant remained closed for one week and specialised work had to be done for the removal of asbestos contained in a wall which was destroyed by the explosion.
It is suspected that the cause of the first incident was a weld on the hydrogen pipe which failed due to fatigue.
Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Main component involved?
Compressor / Booster / Pump
How was it involved?
Leak & Formation Of A Flammable H2-Air Mixture
Initiating cause
Unknown
Root causes
Root CAUSE analysis
The INITIATING (or the contributing) cause is suspected to be the failure of the welding of the hydrogen pipe.
Nothing is known on the root cause, but the organisation has continued the operation, while not able to identify the original of the incidents.

Facility

Application
Chemical Industry
Sub-application
Fertilisers production
Hydrogen supply chain stage
All components affected
compressor, hydrogen pipe, ammonia reactor
Location type
Unknown
Location description
Industrial Area
Operational condition
Pre-event occurrences
other small incidents had occurred during the preceding 7 days : the plant was shut down one week before due to the malfunctioning of a compressor and a boiler. When restarting a small explosion had occurred. The plant was restarted 2 days later and stopped again the next day due to the malfunctioning of an other compressor. After one day of control, the plant is again restarted and the main explosion occurred.

Emergency & Consequences

Number of injured persons
0
Number of fatalities
0
Post-event summary
Asbestos was released by the destruction of a wall. Analysis were made to determine if welded part were strained.
Emergency action
14.30 detection of the leak. Area secured,
19:15 Isolation of the pipeline section
20:00 Start controlled emptying
23:00 Pipeline pressure at zero, start of nitrogen injection
Day after: repair of the leak

Event Nature

Release type
gas mixture
Involved substances (% vol)
H2
NH3
Presumed ignition source
Not reported

References

Reference & weblink

Event 18302 o the French database ARIA<br />
https://www.aria.developpement-durable.gouv.fr/accident/18302_en/?lang=… <br />
(accessed September 2020)